FA2-P0-16-840-41A-BT [Carling Technologies]
Magnetic Circuit Breaker,;型号: | FA2-P0-16-840-41A-BT |
厂家: | Carling Technologies |
描述: | Magnetic Circuit Breaker, 电路保护 |
文件: | 总13页 (文件大小:1882K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
F
F-Se
-Series
rie
s
CIRCUIT BREAKER
The F-Series hydraulic-magnetic high amperage circuit breakers are designed to handle high current applications
in extremely hot and/or cold locations. Due to its time-proven hydraulic-magnetic design, the F-Series load
sensing mechanism is insensitive to changes in ambient or enclosure temperature, providing a consistent trip
point over temperatures ranging from -40°C to +85°C. Additionally, the F-Series circuit breakers come with a
choice of overload time delays, making them ideal for critical applications having inductive loads.
Further, the F-Series breakers are available up to 700A and an optional 25 millivolt metering shunt construction
provides a safe method for monitoring current flowing through the breaker by simply connecting a meter
with light gauge wire to the appropriate terminals located on the shunt housing at the rear of the breaker.
Applications can be customized by measuring and displaying percentage of current, watts or safe/danger zones.
Resources:
Configure a Complete Part
Download CAD & Sales Drawing
Product Highlights:
•ꢀ ACꢀratingsꢀtoꢀULꢀ489
•ꢀ DCꢀvoltageꢀratingsꢀupꢀtoꢀ700Aꢀwithꢀmeteringꢀ
ꢀ shuntꢀsection
•ꢀ Consistentꢀtripꢀpointꢀoverꢀtemperaturesꢀrangingꢀ
ꢀ fromꢀ-40°Cꢀtoꢀ+85°C
Typical Applications:
•ꢀ Idealꢀforꢀapplicationsꢀunderꢀextremeꢀtemperatures
•ꢀ HigherꢀAmperageꢀApplications
•ꢀ BatteryꢀDisconnectꢀSystems
•ꢀ SolarꢀPowerꢀSystems
•ꢀ Military
•ꢀ Optionalꢀ25ꢀmillivoltꢀmeteringꢀshuntꢀconstruction
Carling Technologies, Inc.
60 Johnson Avenue, Plainville, CT 06062
Email: sales@carlingtech.com
Application Support: team2@carlingtech.com
Phone: 860.793.9281 Fax: 860.793.9231
www.carlingtech.com
|
F-Series Circuit Breaker – General Specifications
2
Electrical
Maximum Voltage
Current Ratings
Mechanical
125VDC, 277VAC
Endurance
4000 ON-OFF operations with rated
Current & Voltage & 4000
operations with no load (8000
operations total) @ 5 per minute.
Parallel Pole construction: 1000
operations with rated Current and
Voltage @ 5 per minute.
All F-Series Circuit Breakers will trip
on overload, even when the
actuator is forcibly held in the ON
position.
The operating actuator moves
positively to the OFF position when
an overload causes the circuit
breaker to trip.
Standard current coils: 100, 125,
150, 175, 225, 250 amps. 300,
350, 400, 500, 600, 700 amps
available as parallel pole
construction.
Auxiliary Switch Rating SPDT; 10.1 Amps @ 250VAC, 1.0
Amps @ 65VDC, 0.5 Amps @
Trip Free
80VDC 0.1 Amps @ 125VAC (with
gold contacts).
Minimum: 100 Megohms at 500
VDC
Insulation Resistance
Dielectric Strength
Trip Indication
1960 VAC, 50/60 Hz for one
minute between all electrically
isolated terminals, except 2500
VAC for one minute between
alarm/aux. switch and main
terminals with contacts in open
and closed position. F-Series
circuit breakers comply with the
8mm spacing & 3750VAC 50/60
Hz dielectric requirements from
hazardous voltage to operator
accessible surfaces, between
adjacent poles and from main
circuits to auxilary circuits per
Publications EN 60950 and VDE
0805.
Physical
Number of Poles
1 - 3 Poles Note: Ratings over 250
Amps only available with parallel
pole.
Internal Circuit Config. Series (with or without auxiliary
switch), Switch Only (with or without
auxiliary switch).
Available Accessories Factory installed: DC Current
Metering Shunt (25 mV @lr)
Weight
Varies depending on construction.
Consult factory.
Housing - Black; Actuator- Black or
White with contrasting ON-OFF
legend.
Standard Colors
Resistance, Impedance Values from Line to Load Terminal
- based on Series Trip Circuit
Breaker.
Environmental
Designed and tested in accordance with requirements of
specification MIL-PRF-55629 & MIL-STD-202 as follows:
RESISTANCE PER POLE VALUES
from Line to Load Terminals
(Values Based on Series Trip Circuit Breaker)
Shock
Withstands 100 Gs, 6ms, sawtooth
while carrying rated current per
Method 213, Test Condition “I”.
Instantaneous and ultra-short
curves tested @ 90% of rated
current.
CURRENT
(AMPS)
TOLERANCE
(%)
100 - 700
50
Vibration
Withstands 0.060” excursion from
10-55 Hz, and 10 Gs 55-500 Hz,
at rated current per Method 204C,
Test Condition A. Instantaneous
and ultrashort curves tested at 90%
of rated current.
Moisture Resistance
Method 106D; ten 24-hour cycles @
+ 25°C to +65°C, 80-98% RH.56
days @ +85°C, 85% RH.
Salt Spray
Method 101, Condition A (90-95%
RH @ 5% NaCl Solution, 96 hrs).
Method 107D, Condition A (Five
cycles @ -55°C to +25°C to +85°C
to +25°C).
Thermal Shock
Operating Temperature -40° C to +85° C
*Manufacturer reserves the right to change product specification without prior notice.
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
|
3
F-Series Circuit Breaker – General Specifications
Electrical Tables
Table A: Lists UL Listed (489)and CSA Certified (C22.2 N0. 5.1-M) configurations and performance capabilities as a Molded Case Circuit
Breaker
F SERIES TABLE A : UL489 LISTED BRANCH CIRCUIT BREAKERS
VOLTAGE
CURRENT
RATING
INTERRUPTING
CAPACITY (AMPS)
CIRCUIT
CONFIGURATION
MAX
RATING
FULL LOAD
AMPS
UL / CSA
1 - 3 POLES
TUV 2
1 or 2 POLES
FREQUENCY PHASE
125
DC
---
50 - 250
50,000
25,000
120 / 240 1
50 / 60
50 / 60
50 / 60
1
1
3
100 - 250
100 - 250
100 - 250
10,000
10,000
10,000
---
---
---
SERIES
277
208Y / 120
Notes:
1
2
120/240V rating available in 2 or 3 poles. In a 3 pole construction the center pole is Neutral.
TUV constructions are not available with AC ratings and 150-250 amp ratings only.
Table B: Lists UL Listed configurations and performance capabilities as Circuit Breakers for use in Communications Equipment
(Guide DITT, File E189195), under UL489A
Agency Certifications
IEC 60947-2
UL Listed
UL 489
TUV Certified
Circuit Breakers , Molded Case
(Guide DIVQ, File E129899)
Complies with the requirements
of the CSA Standard for Molded
Case Circuit Breakers,
Low Voltage Switchgear and Control
Gear under TUV License No.
R72031058
CANCSA- C22.2 No. 5.1 –M
Circuit Breakers for Use in
Communications Equipment
(Guide DITT, File E189195)
UL 489A
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
|
4
F-Series Circuit Breaker – Ordering Scheme
F A 2 B 0 14 820 1 2 A B G
8
9
10
12
Agency
Approval
4
5
6
7
11
1
2
3
Terminal
Actuator Mounting
Color
Circuit
Aux/Alarm
Switch
Frequency
& Delay
Current Rating
Max. App.
Rating
Series
Actuator
Poles
12,13
1 SERIES
9 ACTUATOR COLOR & LEGEND
F
Actuator Color
White
I-O
A
ON-OFF
Dual
1
2
Marking Color
Black
White
B
D
Black
C
2 ACTUATOR
A
S
T
Handle, one per pole
Mid-Trip Handle, one per pole
Mid-Trip Handle, one per pole & Alarm Switch
10 MOUNTING
Front Mounting Inserts
Back Mounting Inserts
10-32 screw clearance holes
10-32 screw clearance holes
A
B
10-32
ISO M5
3 POLES
One
1
2
Two
3
Three
11 MAXIMUM APPLICATION RATING
VOLTAGE
125 VDC
120/240
CURRENT
700A
4 CIRCUIT
Parallel Pole Construction:
B
C
F
7
1
3,4
(
)
A
B
C
Switch Only no coil
M
N
P
Series Trip (Current) with Metering Shunt
Switch Only with Metering Shunt
Series Trip (Current)
15
16
250A
3,4
3
3
(
)
Series Trip current
Series Trip voltage
277 VAC
250A
250A
2
(
)
120/208 VAC
Q
Switch Only
12 AGENCY APPROVAL
5
5 AUXILIARY SWITCH
A
G
J
No approvals
0
2
3
4
without Auxiliary Switch
7
S.P.S.T. 0.110 Q.C. Terminals
(Gold Contacts)
S.P.S.T. 0.187 Q.C. Terminals
S.P.D.T. 0.187 Q.C. Terminals
S.P.S.T., 0.093 Round
QC Terminals
UL489 Listed & CUL Certified
S.P.D.T. 0.110 Q.C. Terminals
S.P.D.T. 0.139 Solder Lug
S.P.D.T. 0.110 Q.C. Terminals
(Gold Contacts)
UL489 Listed, CUL Certified & TUV Certified
8
9
A
T
UL489A (Telecom) Listed
6
6
Notes:
5
6
S.P.S.T., 0.093 Q.C. Terminals
(Gold Contacts)
S.P.S.T. 0.110 Q.C. Terminals
1
2
3
For 100 to 250 amps, select Current Code 825. For 300-400 amps, select Current
Code 840. For 450-700 amps, select Current Code 870.
B
S.P.D.T., 0.093 Round
QC Terminals
Available with Frequency and Delay code 10 or 20 only, and are not rated for continuous
duty. Delay 10 and 20 are only available with voltage coils.
3 Codes M, N, P & Q (Parallel Poles) are supplied with factory installed Bus Bar on
Line and Load.
6 FREQUENCY & DELAY
14
16
22
24
26
DC Medium
DC Long
AC Short
AC Medium
AC Long
4
5
4 Metering terminals are female pin type, ref. Molex part number 02-09-1101, model 1189-T.
Auxiliary Switch breakers are only available with Series Trip and Switch Only circuits.
On multi-pole breakers, one Auxiliary Switch is supplied, mounted in the extreme right
pole per figure A. Back-Mounted breakers require special mounting provisions when
an Auxiliary Switch is specified.
Available with parallel pole construction (circuit codes P and Q, and breakers with
circuit codes M and N).
Frequency and delay code 10 is only available with Voltage Coils. Voltage Coils are not
rated for continuous duty.
Ratings over 250 amps are only available with Agency Approval code T (UL489A) and
are Parallel Pole configuration (circuit codes M, N, P and Q.) 300-450 amp ratings are
available on two pole breakers. 500-700 amp ratings are available on three pole
breakers.
Per UL requirement, an “Anti-Flash Over Barrier” is supplied between poles on multipole
breakers with 3/8 - 16 stud terminals (Terminal Code 1) on AC rated breakers only.
03
10
11
12
DC 50/60Hz, Switch Only
DC Instantaneous
DC Ultra Short
7
DC Short
6
7
8
7 CURRENT RATING (AMPERES)
CODE AMPERES
8
8
8
8
8
810 100.000
912 125.00
815 150.00
917 175.00
820 200.00
922 225.00
825 250.00
835 350.00
860 600.00
8
840 400.00
870 700.00
845 450.00
9
8
830 300.00
850 500.00
10 Front connected breakers can also be front mounted by utilizing the supplied front panel
mounting inserts. Terminal connections must be made before mounting.
11 Box Wire connector will accept #6 through 250 MCM copper wire.
12 Agency codes G & T must have ON-OFF or dual legends. Agency code J must have
dual legend.
7
OR VOLTAGE COIL (MIN. TRIP RATING, VOLTS)
CODE AMPERES
A06 6 DC, 5 DC
A12 12 DC, 10 DC
A18 18 DC, 15 DC
A24 24 DC, 20 DC
A32 32 DC, 25 DC
A48 48 DC, 40 DC
A65 65 DC, 55 DC
B25 125 DC, 100 DC
J06 6 AC, 5 AC
13 Other colors available. Consult factory.
14 Terminals 2,4 & 5 are shipped without terminal hardware.
15 2 or 3 Pole Circuit Breaker Required for 120/240 VAC Rating.
16 3 Pole Circuit Breaker Required for 120/208 VAC Rating.
8 TERMINAL
Back Connected (Front Mounted Only)
Max Rating
250A
9
14
14
1
2
5
3/8-16 Stud
3/8-16 Screw, Line & Load
3/8-16 Short Stud
700A
250A
11
Front Connected (Back Mounted Only)
Max Rating
700A
3
4
Box Wire Connector, Line & Load
3/8-16 Screw, Line & Load
14
700A
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
|
5
F-Series Circuit Breaker – Circuit & Terminal Diagrams
Circuit & Terminal Diagrams: in. [mm]
Notes:
1
2
All dimensions are in inches [millimeters].
Tolerance ±.020 [.51] unless otherwise specified.
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
|
6
F-Series Circuit Breaker – Circuit & Terminal Diagrams
Circuit & Terminal Diagrams: in. [mm]
Notes:
1
2
All dimensions are in inches [millimeters].
Tolerance ±.020 [.51] unless otherwise specified.
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
|
7
F-Series Circuit Breaker – Dimensional Specifications
Dimensional Specifications: in. [mm]
Notes:
1
2
All dimensions are in inches [millimeters].
Tolerance ±.020 [.51] unless otherwise specified.
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
|
8
F-Series Circuit Breaker – Dimensional Specifications
Dimensional Specifications: in. [mm]
Notes:
1
2
All dimensions are in inches [millimeters].
Tolerance ±.020 [.51] unless otherwise specified.
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
|
9
F-Series Circuit Breaker – Dimensional Specifications
Dimensional Specifications: in. [mm]
F-Series breakers are available up to 700A, and are also available with a 25 millivolt metering shunt construction.
This optional construction provides a safe method for monitoring current flowing through the breaker by simply
connecting a meter with light gauge wire to the appropriate terminals located on the shunt housing at the rear of
the breaker. You can customize the application by measuring and displaying percentage of current, watts or safe/
danger zones.
Notes:
1
2
All dimensions are in inches [millimeters].
Tolerance ±.020 [.51] unless otherwise specified.
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
|
10
F-Series Circuit Breaker – Dimensional Specifications
Dimensional Specifications: in. [mm]
Notes:
1
2
All dimensions are in inches [millimeters].
Tolerance ±.020 [.51] unless otherwise specified.
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
|
11
Time Delay Values – F-Series Circuit Breaker
.008 - .032
.140 - .850
2.50 - 15.0
22.0 - 150
0.13 - 0.90
2.00 - 18.0
14.0 - 150
.005 - .020
.015 - .125
.180 - 1.00
1.00 - 5.50
.004 - .020
.010 - .050
.010 - .280
.010 - 1.80
11
12
14
16
22
24
26
No Trip
No Trip
No Trip
No Trip
No Trip
No Trip
No Trip
.013 - .125
.475 - 10.0
10.0 - 110
110 - 1000
0.44 - 10.0
7.20 - 110
100 - 1100
.010 - .070
.275 - 2.80
6.00 - 40.0
60.0 - 400
0.25 - 2.80
4.40 - 45.0
32.0 - 400
.006 - .020
.030 - .190
.500 - 3.00
4.00 - 25.0
.004 - .020
.008 - .038
.008 - .080
.008 - .390
0.030 - 0.19 0.015 - 0.125 0.010 - 0.055 0.008 - 0.045
0.25 - 3.50
2.50 - 25.0
0.016 - 1.60
0.020 - 11.0
0.009 - 0.33
0.010 - 3.10
0.008 - 0.11
0.008 - 0.39
AC
DC
Short - AC 22
Ultrashort - DC
F SERIES
50/60 HZ SHORT
CURVE NO. 22
PERCENT OF RATED CURRENT
Short - DC
PERCENT OF RATED CURRENT
Medium - AC 24
F SERIES
50/60 HZ MEDIUM
CURVE NO. 24
PERCENT OF RATED CURRENT
Medium - DC
PERCENT OF RATED CURRENT
Long - AC 26
F SERIES
50/60 HZ LONG
CURVE NO. 26
PERCENT OF RATED CURRENT
Long - DC
PERCENT OF RATED CURRENT
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
|
12
Sales Representatives, Distributors & Company Profile
Authorized Sales Representatives and Distributors
Click on a region of the map below to find your local representatives and distributors or visit
www.carlingtech.com/findarep.
CANADA
EUROPE
USA
MIDDLE
EAST
MEXICO
AFRICA
ASIA-PACIFIC
OCEANIA
SOUTH
AMERICA
About Carling
Founded in 1920, Carling Technologies is a leading manufacturer of electrical and electronic switches
and assemblies, circuit breakers, electronic controls, power distribution units, and multiplexed power
distribution systems. With four ISO registered manufacturing facilities and technical sales offices worldwide,
Carling Technologies Sales, Service and Engineering teams do much more than manufacture electrical
components, they engineer powerful solutions! To learn more about Carling please visit
www.carlingtech.com/company-profile.
To view all of Carling’s environmental, quality, health & safety certifications please visit
www.carlingtech.com/environmental-certifications
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
Worldwide Headquarters
Carling Technologies, Inc.
60 Johnson Avenue, Plainville, CT 06062
Phone: 860.793.9281 Fax: 860.793.9231
@
Email: sales carlingtech.com
@
Northern Region Sales Office: nrsm carlingtech.com
@
Southeast Region Sales Office: sersm carlingtech.com
@
Midwest Region Sales Office: mrsm carlingtech.com
@
West Region Sales Office: wrsm carlingtech.com
@
Latin America Sales Office: larsm carlingtech.com
Asia-Pacific Headquarters
Carling Technologies, Asia-Pacific Ltd.,
Suite 1607, 16/F Tower 2, The Gateway,
Harbour City, 25 Canton Road,
Tsimshatsui, Kowloon, Hong Kong
Phone: Int + 852-2737-2277 Fax: Int + 852-2736-9332
@
Email: sales carlingtech.com.hk
@
Shenzhen, China: shenzhen carlingtech.com
@
Shanghai, China: shanghai carlingtech.com
@
Pune, India: india carlingtech.com
@
Kaohsiung, Taiwan: taiwan carlingtech.com
@
Yokohama, Japan: japan carlingtech.com
|
|
Europe Middle East Africa Headquarters
Carling Technologies LTD
4 Airport Business Park, Exeter Airport,
Clyst Honiton, Exeter, Devon, EX5 2UL, UK
Phone: Int + 44 1392.364422 Fax: Int + 44 1392.364477
@
Email: ltd.sales carlingtech.com
@
Germany: gmbh carlingtech.com
@
France: sas carlingtech.com
www.carlingtech.com
REV_01_2019
相关型号:
FA2005H5E3000
Card Edge Connector, 5 Contact(s), 1 Row(s), Female, Right Angle, Surface Mount Terminal
JAE
FA2006H5E3000
Card Edge Connector, 6 Contact(s), 1 Row(s), Female, Right Angle, Surface Mount Terminal
JAE
FA2007H5E3000
Card Edge Connector, 7 Contact(s), 1 Row(s), Female, Right Angle, Surface Mount Terminal
JAE
FA2008H5E3000
Card Edge Connector, 8 Contact(s), 1 Row(s), Female, Right Angle, Surface Mount Terminal
JAE
FA2009H5E3000
Card Edge Connector, 9 Contact(s), 1 Row(s), Female, Right Angle, Surface Mount Terminal
JAE
FA2010H5E3000
Card Edge Connector, 10 Contact(s), 1 Row(s), Female, Right Angle, Surface Mount Terminal
JAE
FA2012H5E3000
Card Edge Connector, 12 Contact(s), 1 Row(s), Female, Right Angle, Surface Mount Terminal
JAE
FA2013H5E3000
Card Edge Connector, 13 Contact(s), 1 Row(s), Female, Right Angle, Surface Mount Terminal
JAE
FA2014H5E3000
Card Edge Connector, 14 Contact(s), 1 Row(s), Female, Right Angle, Surface Mount Terminal
JAE
©2020 ICPDF网 联系我们和版权申明